Petronas Twin Towers - Malaysia

Kuala Lumpur City Centre Project, Malaysia

Petronas Twin Towers, the tallest buildings in the world, utilize 24 R-B fire pumps for fire protection.
These pumps range in capacity from 500-1250 GPM, and the pressure heads range from 392-940 feet.

R-B Pump Home Page          Split-Case Fire Pump Installation 


DESCRIPTION OF THE FIRE PUMP SYSTEMS FOR THE PETRONAS TWIN TOWERS
Pump Size
Flow Rate
Pressure Head
Quantity
3x3 LDF
500 GPM
392 feet
2
3x3 LDF
500 GPM
521 feet
2
5x5 LDF
750 GPM
542 feet
2
6x6 LDF
1250 GPM
404 feet
2
6x5 TF
500 GPM
647 feet
2
6x5 TF
500 GPM
728 feet
2
6x5 TF
500 GPM
878 feet
2
6x5 TF
500 GPM
924 feet
2
6x5 TF
750 GPM
795 feet
2
6x5 TF
750 GPM
940 feet
2
6x5 TF
1000 GPM
715 feet
2
6x5 TF
1000 GPM
900 feet
2